DIRECT VENT
GAS FIREPLACE HEATER
MODEL SERIES
MILLIVOLT STANDING PILOT
DVP42FP3(0,1,2,3)(N,P)-2
DVP48FP3(0,1,2,3)(N,P)-2
INTERMITTENT PILOT
DVP42FP7(0,1,2,3)(N,P)-2
DVP48FP7(0,1,2,3)(N,P)-2
REMOTE RF MODELS
DVP42FP9(1,3)(N,P)-2
DVP48FP9(1,3)(N,P)-2
UL FILE NO. MH30033
INSTALLATION INSTRUCTIONS
AND
OWNER’S MANUAL
WARNING: If not installed, operated and maintained
in accordance with the manufacturer’s instructions,
this product could expose you to substances in fuel or
from fuel combustion which can cause death or seri-
ous illness.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA only)
or mobile home, where not prohibited by state or local
codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified
kit is used.
The Tahoe Direct Vent Zero Clearance
Gas Fireplace Heater
GAS-FIRED
Installer: Leave this manual with the appli-
ance.
Consumer: Retain this manual for future refer-
ence.
— Do not store or use gasoline or other flamma-
ble vapors and liquids in the vicinity of this or
any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppli-
er’s instructions.
If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
WARNING: If the information in these instruc-
tions are not followed exactly, a fire or explosion
may result causing property damage, personal
injury or loss of life.
Page 1
Seitenansicht 0
1 2 3 4 5 6 ... 71 72

Inhaltsverzeichnis

Seite 1 - OWNER’S MANUAL

DIRECT VENT GAS FIREPLACE HEATERMODEL SERIESMILLIVOLT STANDING PILOTDVP42FP3(0,1,2,3)(N,P)-2DVP48FP3(0,1,2,3)(N,P)-2INTERMITTENT PILOTDVP42FP7(0,1,2,3

Seite 2 - TABLE OF CONTENTS

21759-6-0608Page 10REAR VENT CONVERSIONConverting flue take-off to rear ventingWhen switching out the flue and inlet vent collars to run horizontally of

Seite 3

21759-6-0608 Page 11Framing and Finishing 1. Choose unit location. 2. Frame in fireplace with a header across the top. It is important to allow fo

Seite 4 - 21759-6-0608Page 4

21759-6-0608Page 12DVP42 DVP48"A" 37 3/4" 37 3/4""B" 43 3/8" 49 3/8""C" 19 7/8" 19 7/8"Fig

Seite 5 - 21759-6-0608 Page 5

21759-6-0608 Page 13Flush Wall InstallationFigure 12Combustible Surround InstallationFigure 13Vent Runs (Figures 14, 15, 16, 17 and 18)In planning the

Seite 6 - INTRODUCTION

21759-6-0608Page 14HORIZONTAL ONLY, STRAIGHT OUT THE BACKFigure 15VERTICAL, 90° ELBOW TO HORIZONTAL OUT THE WALLCORNER INSTALLATION VERTICAL, 90° ELBO

Seite 7 - FIREPLACE DIMENSIONS

21759-6-0608 Page 15To Use the Vent Graph (Figure 19)1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the S

Seite 8 - LOCATING FIREPLACE

21759-6-0608Page 16Figure 21Examples of possible venting systems using two (2) 90° elbows. V is listed as minimum vertical dimensions and H1 + H2 is

Seite 9 - GAS SUPPLY

21759-6-0608 Page 17MAXIMUM HORIZONTALRUN WITH NO VERTICALRISE AND 90° ELBOWMAXIMUM HORIZONTALRUN WITH MINIMUMVERTICAL RISE AND90° ELBOWminimumFigure

Seite 10 - VENT SYSTEMS

21759-6-0608Page 18Figure 26Figure 27Figure 2824”24” MINIMUMCLEARANCE TOCOMBUSTIBLESEXAMPLES - TOP VENT RUN

Seite 11 - INSTALLATION

21759-6-0608 Page 19VENTING EXAMPLES WHEN USING DVA47 ADAPTORVertically Off Top of Fireplace OnlyFigure 29Figure 30Figure 31

Seite 12 - INSTALLATION (continued)

21759-6-0608Page 2Important Safety Information ...

Seite 13 - 21759-6-0608 Page 13

21759-6-0608Page 20Installation InstructionsThis termination kit can only be used with Empire Comfort Systems direct vent fireplaces listed for use wit

Seite 14

21759-6-0608 Page 21PRE-INSTALLATION INFORMATION:Items Required For Installation:Tools Building SuppliesPhillips ScrewdriverHammerSaw and/or saber saw

Seite 15 - VENTING FIREPLACE - TOP

21759-6-0608Page 221. Unpack vent components and check all items for shipping damage.2. For this venting system to operate as designed

Seite 16 - Firestop at

21759-6-0608 Page 2310. With the flex vent assembly and the 48” long hard pipe components laid out on the floor, begin securing these parts t

Seite 17 - 21759-6-0608 Page 17

21759-6-0608Page 2417. To attach the vent connections at the fireplace, be sure the 7” diameter adapter collar has been installed per step 3. Apply a

Seite 18 - EXAMPLES - TOP VENT RUN

21759-6-0608 Page 25Figure 38StormClearance toCombustiblesCollarExteriorRoofRoofFlashingRoof JackAdjustableAssembly4' Long Rigid PipeDirect VentF

Seite 19 - Figure 31

21759-6-0608Page 26Vertical Flex Termination KitItem Number Item Description Repair Part No.Quantity Supplied1 4”/7” Vertical Termination Cap MF100038

Seite 20 - IMPORTANT SAFETY INFORMATION

21759-6-0608 Page 27Figure 39 Acceptable vertical and horizontal vent run. Unacceptable vertical and horizontal vent run.Venting Graph (Dimensions i

Seite 21 - PRE-INSTALLATION INFORMATION:

21759-6-0608Page 28Figure 40Figure 41Figure 42Figure 43Model Maximum Pipe Length H1DVP42 24"DVP48 18"Model Maximum Pipe Length H1DVP42 24&qu

Seite 22 - (4) REQ'D

21759-6-0608 Page 29CAUTION: Sharp edges, use protective gloves when installing.Tools Needed for Installation:Sheet metal snips5/16” nut driver

Seite 23 - 21759-6-0608 Page 23

21759-6-0608 Page 3DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLEDBefore enclosing the vent pipe assembly, operate the appliance to

Seite 24 - INTAKE PIPE

21759-6-0608Page 307. Remove outside mounting plate with tube attached from wall. Mark and cut the extra length of the 6 5/8” (168mm) diameter tube f

Seite 25 - Fireplace

21759-6-0608 Page 31Follow correct option according to venting method.Connecting Directly to FireplaceIf the air inlet and flue outlet tubes are to be

Seite 26 - Vertical Flex Termination Kit

21759-6-0608Page 32INSTALLATION1. Unpack vent components and check that all items are included.2. Check to see that the vent spacer springs are lo

Seite 27 - VENTING FIREPLACE - REAR

21759-6-0608 Page 33Termination clearance for buildings with combustible and noncombustible exteriors.Vertical Sidewall InstallationsImportant! Minimu

Seite 28 - EXAMPLES - REAR VENT RUN

21759-6-0608Page 34Figure 55A = *Clearance above grade, veranda, porch, deck or balcony [*12 inches (30cm) minimum]B = clearance to window or door

Seite 29 - INSTALLED TO TOPSIDE

21759-6-0608 Page 35Installing Vent Components (Figure 56)Begin the vent system installation by installing the first Simpson Duravent component, 90° el

Seite 30 - VINYL SIDING KIT

21759-6-0608Page 36Installing Vent Components (Figure 57)Begin the vent system installation by installing the first Simpson Duravent component, 90° elb

Seite 31 - 21759-6-0608 Page 31

21759-6-0608 Page 37Installing Support Brackets (Figure 58)A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports

Seite 32

21759-6-0608Page 38Figure 60Figure 62See Horizontal Termination Page 41 and Vertical Termination Pages 43 and 44.Figure 618" VENTING FRAMING AND

Seite 33 - TERMINATION CLEARANCES

21759-6-0608 Page 39Installing Support Brackets (Figure 63)A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pi

Seite 34 - VENT CLEARANCES

21759-6-0608Page 4Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you can smell

Seite 35 - Figure 56

21759-6-0608Page 40Figure 67See Horizontal Termination Page 41 and Vertical Termination on Pages 43 and 44.6 ⅝" VENTING FRAMING AND FINISHING (co

Seite 36

21759-6-0608 Page 41NOTE: Termination cap should pass through the wall firestop from the exterior of the building. Adjust the termination cap t

Seite 37 - 21759-6-0608 Page 37

21759-6-0608Page 42INSTALLATION1. Unpack vent components and check that all items are included.2. Check to see that the vent spacer springs are lo

Seite 38 - Figure 61

21759-6-0608 Page 43Locate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this nail through this c

Seite 39 - 21759-6-0608 Page 39

21759-6-0608Page 44Reassembly and Resealing Gas Accumulation Relief SystemGlass Frame Assembly and Combustion ChamberWhenever the glass frame assembly

Seite 40 - Figure 66

21759-6-0608 Page 45WARNING: Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this

Seite 41 - HORIZONTAL TERMINATION

21759-6-0608Page 46The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the g

Seite 42 - VENT PIPE

21759-6-0608 Page 47STANDING PILOT OPERATING INSTRUCTIONS Remote/Off/On SwitchThe fireplace is equipped with a Remote/OFF/ON switch. A wire harness is

Seite 43 - VERTICAL TERMINATION

21759-6-0608Page 48Figure 82(OPTIONAL) THERMOSTAT(OPTIONAL) WALL SWITCHSTANDING PILOT WIRING DIAGRAM

Seite 44 - 21759-6-0608Page 44

21759-6-0608 Page 491. Stop! Read the safety information above.2. Set REMOTE/OFF/ON switch to OFF.3. Turn off all electric power to the appliance (

Seite 45 - LOG PLACEMENT (4 LOG SET)

21759-6-0608 Page 5REQUIREMENTS FOR MASSACHUSETTSFor all side wall horizontally vented gas fueled equipment installed in every dwelling, building or s

Seite 46 - HI/LO REGULATO

21759-6-0608Page 50With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do

Seite 47 - 21759-6-0608 Page 47

21759-6-0608 Page 511. To wire Junction Box Receptacle, remove the tab on the side of the receptacle (hot side) to split receptacle. This will be req

Seite 48 - (OPTIONAL) WALL SWITCH

21759-6-0608Page 521. Stop! Read the safety information above.2. Set the thermostat to lowest setting.3. Turn off all electric power to the applian

Seite 49 - TO TURN OFF GAS TO FIREPLACE

21759-6-0608 Page 53GENERAL: All fireplaces have been fire-tested to check for proper operation. This includes, main burner flame, pilot flame, fan oper

Seite 50 - 21759-6-0608Page 50

21759-6-0608Page 54spark generator and energizes the second main valve operator. The second main valve opens and gas flows to the main burner, where i

Seite 51 - 21759-6-0608 Page 51

21759-6-0608 Page 55Important 1. The following service procedures are provided as a general guide. 2. Meter readings between gas control and ign

Seite 52 - HONEYWELL

21759-6-0608Page 56INTERMITTENT PILOT TROUBLESHOOTING (continued)

Seite 53 - 21759-6-0608 Page 53

21759-6-0608 Page 57INTERMITTENT PILOT TROUBLESHOOTING (continued)Green LED Status CodesGreen LED Flash Code (X + Y)aIndicates Next System Action Reco

Seite 54 - 21759-6-0608Page 54

21759-6-0608Page 58Functions• Flame powered system• Flame powered flame modulation• Electronics integrated into valve to provide thermostat, flame, a

Seite 55 - 21759-6-0608 Page 55

21759-6-0608 Page 59FIRST USE OF TRANSMITTERStatus ActionBegin communication between transmitter and receiver/valve. Move LOCAL/REMOTE Switch to LOCAL

Seite 56 - 21759-6-0608Page 56

21759-6-0608Page 6Instructions to Installer1. Installer must leave instruction manual with owner after installation.2. Installer must have ow

Seite 57 - 21759-6-0608 Page 57

21759-6-0608Page 60WIRING DIAGRAM WITH BLOWERFigure 85RF WIRING DIAGRAM

Seite 58 - 21759-6-0608Page 58

21759-6-0608 Page 611. STOP! Read the safety information above.2. Turn off all electric power to the appliance (if applicable).3. Lower lou

Seite 59 - RF TRANSMITTER FUNCTIONS

21759-6-0608Page 62Please NoteIt is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up

Seite 60 - WIRING DIAGRAM WITH BLOWER

21759-6-0608 Page 6315*1212789101112201913122322a21171816123456111427282931302433323440384239a36a37a415239b34333224302928273136b444637b33343236c37c312

Seite 61 - TO TURN OFF GAS TO APPLIANCE

21759-6-0608Page 64INDEX NO. PART NUMBER DESCRIPTIONDVP42 DVP481R-7654 R-7654 FLUE INSULATION2 17426 17426 FLUE INSULATION RETAINER3R-7567 R-7567 INLE

Seite 62 - MAINTENANCE AND SERVICE

21759-6-0608 Page 65INDEX NO. PART NUMBER DESCRIPTIONDVP42 DVP4826P200 P200 ORIFICE FITTING27P203 P213 ORIFICE (NAT)27P185 P250 ORIFICE (LP)28R-5676 R

Seite 63 - PARTS VIEW

21759-6-0608Page 66Attention: Install blower assembly before connecting gas inlet supply lineNote: Junction box on right side of fireplace must be p

Seite 64 - PARTS LIST

21759-6-0608 Page 67110 VOLT ACJUNCTION BOXWHITESPEEDCONTROLFANSWITCHGROUNDBLACKFAN1 FBB4 B L O W E R A S S E M B LY COMPLETE2 R7649 FAN CONTROL3 R4

Seite 65 - PARTS LIST (continued)

21759-6-0608Page 68CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE B

Seite 66 - 21759-6-0608Page 66

21759-6-0608 Page 69The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond w

Seite 67 - 110 VOLT AC

21759-6-0608 Page 7Figure 1DVP42 DVP48A 43"1092mm49"1245mmB 40"1016mm46"1168mmC 25 1/16"636 mm25 1/16"636 mmD 37 5/8&quo

Seite 68 - 21759-6-0608Page 68

21759-6-0608Page 70Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts

Seite 69 - ACCESSORIES

21759-6-0608 Page 71SERVICE NOTES

Seite 70 - HOW TO ORDER REPAIR PARTS

21759-6-0608Page 72Empire Comfort Systems, Inc.918 Freeburg Ave. Belleville, IL 62220PH: 618-233-7420 or 800-851-3153FAX: 618-233-7097 or 800-443-864

Seite 71

21759-6-0608Page 8Mantel Chart (Figure 3)Figure 3Clearances (Figure 4)Clearance from top front edge of fireplace to ceiling is 36"Clearance from s

Seite 72

21759-6-0608 Page 9Figure 6 The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas